Grid Compensation & Power Quality · Part 3 of 4

The brain: cascaded control loops

A fast current loop, a slower DC-voltage loop and a sudden reactive-power reversal.

01

Live experiment

Educational example · phase RMS quantities · balanced three-phase system

Kp=13.64, Ti=17.37 msK_p=13.64,\ T_i=17.37\,\mathrm{ms}
02 msA
i*i
Ideal current reversal · first 2 ms
060 msV
E(t)
DC energy envelope · 60 ms
Proportional gain
13.64 V/A
Integration time
17.37 ms
Transient energy
40.71 J
DC voltage dip
2.44 %

02

Model & equations

Pole-zero cancellation makes the ideal inner loop first order. The voltage trace uses a 1 ms energy extraction followed by a 15 Hz exponential recovery; it is an energy-envelope illustration, not a full switching simulation.

Gi(s)=1Ls+R,Ci(s)=Kp(1+1Tis),Kp=2πfloopL,Ti=LRG_i(s)=\frac1{Ls+R},\quad C_i(s)=K_p\left(1+\frac1{T_i s}\right),\quad K_p=2\pi f_{loop}L,\quad T_i=\frac LR
i(s)i∗(s)=ωloops+ωloop,ΔW=QcompΔt\frac{i(s)}{i^*(s)}=\frac{\omega_{loop}}{s+\omega_{loop}},\quad \Delta W=Q_{comp}\Delta t
Edip=E2−2ΔWC,ΔE%=100(1−EdipE)E_{dip}=\sqrt{E^2-\frac{2\Delta W}{C}},\quad \Delta E\%=100\left(1-\frac{E_{dip}}E\right)

03

Example parameters

Vg
230 V RMS
f
50 Hz
E
750 V
Rcc
0.05 Ω
Xcc
0.1 Ω
R
0.05 Ω
Rf
0.6 Ω
P
80 kW
cos φ
0.74
fc
10 kHz
L
0.87 mH
Δt
1 ms