Grid Compensation & Power Quality · Part 1 of 4

The grid & the pollution problem

Phase lag, reactive power and the harmonic fingerprint of a non-linear load.

01

Live experiment

Educational example · phase RMS quantities · balanced three-phase system

040 msp.u.
VoltageCurrent
Normalized waveforms · voltage / peak, current / fundamental peak
h1100%h50%h70%h110%h130%
Harmonic amplitudes · % of fundamental
Diode bridge
Reactive load power
72.71 kvar
Current THD
0 %
Voltage drop
16.34 V
True power factor
0.74

02

Model & equations

The red current lags the voltage by φ. With the diode bridge enabled, the same fundamental carries 5th, 7th, 11th and 13th harmonics. This truncated Fourier model is illustrative, not a detailed diode commutation simulation.

Q=Ptan⁡(arccos⁡(cos⁡φ)),I1=P3Vgcos⁡φQ=P\tan(\arccos(\cos\varphi)),\qquad I_1=\frac{P}{3V_g\cos\varphi}
THDi=∑h∈{5,7,11,13}(Ih/I1)2,Ih/I1=1/h\mathrm{THD}_i=\sqrt{\sum_{h\in\{5,7,11,13\}}(I_h/I_1)^2},\quad I_h/I_1=1/h
ΔV≈RccP+XccQ3Vg,PF=cos⁡φ1+THDi2\Delta V\approx\frac{R_{cc}P+X_{cc}Q}{3V_g},\qquad \mathrm{PF}=\frac{\cos\varphi}{\sqrt{1+\mathrm{THD}_i^2}}

03

Example parameters

Vg
230 V RMS
f
50 Hz
E
750 V
Rcc
0.05 Ω
Xcc
0.1 Ω
R
0.05 Ω
Rf
0.6 Ω
P
80 kW
cos φ
0.74
fc
10 kHz
L
0.87 mH
Δt
1 ms